PPE(UL94-V0)*Flammability resistance can
be available upon request.
I2-Thread lead alloy recessed terminal to accept M6/M8 bolt
13.5 to 13.8 VDC/unit Average at 25 (77 )
14.4 to 15.0 VDC/unit Average at 25 (77 )
Cells per unit
Voltage per unit
Capacity
Weight
Maximum Discharge Current
Internal Resistance
Operating Temperatur e Range
Nominal Operating Temperature Range
Float Charging Voltage
Recommended Maximum Charging
Current Limit
Equalization and Cycle Service
Self Discharge
Terminal
Container Material
6
12
500W @ 15min-rate to 1.67V per cell @25
o
C(77
o
F)
Approx.45.7 kg(100.75 lbs)
800A(5sec)
Approx. 3.7
m
25
o
C±3
o
C (77
o
F±5
o
F)
50A
CSB Batteries can be stored for more than 6 months at
25
o
C (77
o
F). Please charge batteries before using. For
higher temperatures the time interval will be shorter.
Discharge: -15 ~50 ( 5 ~122 )
Charge: -15
~40 ( 5 ~104 )
Storage: -15
~40 ( 5 ~104 )
Constant Power Discharge Characteristics
Unit:W
(25
,77
)
Constant Current Discharge Characteristics
Unit:A
(25
,77
)
HRL 12500W
12V 500W
Specification
Powered by
HRL 12500W is specially designed for high efficient discharge
application. Its characteristics are high energy density, small
footprint and high discharge efficiency. It can be used for more
than 260 cycles at 100% discharge in cycle service, up to 10
years in standby service.
Width (W)
Dimensions :
Unit: mm (inch)
Overall Height (H) Container height (h) Length (L)
277.7±2.5(10.93±0.10) 274.7±2.5 (10.81±0.10) 343.0 ±2.5 (13.50±0.10) 170.0±2.0 (6.69±0.08)
F.V/Time
5MIN 7.5MIN 10MIN 15MIN 20MIN 30MIN 40MIN 50MIN 60MIN 90MIN
1.60V
491 444 388 294 235 172 136 112 95.7 67.2
1.67V
449 405 356 278 223 164 134 110 94.3 66.1
1.70V
425 386 340 270 217 161 133 109 93.5 65.4
1.75V
388 348 310 253 206 155 130 107 91.1 64.5
1.80V
348 309 278 233 194 147 123 102 87.3 62.0
1.85V
304 270 247 211 179 140 115 95.3 81.1 57.3
F.V/Time
5MIN 7.5MIN 10MIN 15MIN 20MIN 30MIN 40MIN 50MIN 60MIN 90MIN
1.60V
5,275 4,691 4,167 3,181 2,594 1,951 1,558 1,292 1,112 783
1.67V
4,880 4,300 3,790 3,018 2,490 1,871 1,520 1,276 1,091 769
1.70V
4,640 4,110 3,610 2,932 2,422 1,829 1,507 1,258 1,083 763
1.75V
4,250 3,750 3,290 2,748 2,309 1,740 1,466 1,237 1,066 754
1.80V
3,830 3,340 2,950 2,497 2,138 1,657 1,390 1,186 1,025 731
1.85V
3,366 2,882 2,600 2,203 1,964 1,564 1,321 1,130 977 695
CSB-manufactured
VRLA batteries are UL-
recognized components
under UL1989.
CSB is also certified by
ISO 9001 and ISO 14001.
RA1308
Ratings presented herein are subject to revision without notice. Please refer to www.csb-battery.com to confirm the latest version.
Seitenansicht 0
1 2

Inhaltsverzeichnis

Seite 1 - HRL 12500W

PPE(UL94-V0)*Flammability resistance can be available upon request.I2-Thread lead alloy recessed terminal to accept M6/M8 bolt13.5 to 13.8 VDC/unit Av

Seite 2

68Charging ProceduresCharge Voltage(V/Cell)ApplicationTemperature Set Point Allowable RangeMax.Charge CurrentCycle Use25(77 )2.45 2.40~2.50Standby25 (

Kommentare zu diesen Handbüchern

Keine Kommentare