Cells Per Unit 6
Voltage Per Unit 12
Capacity
360W @ 5min-rateto Watt(1.60V)/pcs @25°C (77°F)
Weight Approx. 1.97 kg(4.34 lbs)
Maximum Discharge Current 100/130A(5sec)
Internal Resistance Approx. 22mΩ
Operating Temperature Range
Nominal Operating Temperature Range
Float Charging Voltage 13.5 to 13.8 VDC/unit Average at
Recommended Maximum Charging 3.0A
Current Limit
Equalization and Cycle Service 14.4 to 15.0 VDC/unit Average at
Self Discharge CSB Batteries can be stored for more than 6 months at
Please charge batteries before using. For
higher temperatures the time interval will be shorter.
Terminal
Container Material
Discharge:
Charge:
Storage:
F1/F2-Faston Tab 180/250
ABS(UL 94-HB) & Flammability resistance of
(UL 94-V0) can be available upon request.
Constant Power Discharge Characteristics Unit:W (25°C,77°F)
Constant Current Discharge Characteristics Unit:A (25°C,77°F)
UPS123606
Specification
Powered by
UPS 123606 is specially designed for high efficient discharge
application. Its characteristics are high energy density, small
footprint and high discharge efficiency. It can be used for more
than 260 cycles at 100% discharge in cycle service, up to 5 years
in standby service.
Width (W)
Dimensions :
Unit: mm (inch)
Overall Height (H) Container height (h) Length (L)
98.3±1.0 (3.87±0.04) 94.0±1.0 (3.70±0.04) 151.0±2.0 (5.94±0.08) 51.0±1.0 (2.01±0.04)
CSB-manufactured
VRLA batteries are UL-
recognized components
under UL1989.
CSB is also certified by
ISO 9001 and ISO 14001.
(http://www.csb-battery.com)
by URS according to ISO 9001,ISO 14001.
The system of manufacturer was certified
F.V/Time 2MIN 3MIN 4MIN 5MIN 6MIN 7MIN 8MIN 10MIN 15MIN 20MIN 30MIN 60MIN 90MIN
1.60V
61.7 49.0 41.2 35.3 31.1 27.7 24.7 20.7 15.2 12.1 8.90 5.10 3.64
1.67V
55.0 45.7 38.8 33.7 30.1 26.7 24.0 20.4 15.1 12.1 8.84 5.06 3.62
1.70V
52.2 43.8 37.5 32.6 29.2 26.0 23.6 20.1 15.0 12.0 8.81 5.02 3.61
1.75V
47.1 40.0 34.6 30.8 27.2 24.6 22.5 19.2 14.6 11.8 8.68 4.97 3.58
1.80V
42.4 36.0 31.4 27.6 24.8 22.4 20.7 18.0 13.9 11.3 8.40 4.88 3.52
1.85V
36.8 31.3 27.0 24.1 21.7 20.1 18.5 16.4 12.7 10.5 7.95 4.63 3.38
F.V/Time 2MIN 3MIN 4MIN 5MIN 6MIN 7MIN 8MIN 10MIN 15MIN 20MIN 30MIN 60MIN 90MIN
1.60V
558 467 403 360 318 284 259 222 169 135 100.0 58.4 42.4
1.67V
529 444 388 347 308 277 254 218 167 134 99.1 58.0 42.3
1.70V
510 436 381 340 301 272 250 216 165 133 98.7 57.7 42.0
1.75V
472 408 364 319 287 261 238 210 159 132 98.2 57.3 41.7
1.80V
423 376 330 293 264 244 225 199 154 126 96.0 56.4 41.2
1.85V
374 324 287 261 238 220 204 183 142 119 91.7 54.6 40.2
25°C (77°F)
25°C (77°F)
25°C (77°F).
-15°C~50°C ( 5°F~122°F)
-15°C~40°C ( 5°F~104°F)
-15°C~40°C ( 5°F~104°F)
25°C±3°C (77°F±5°F)
RA1308
Ratings presented herein are subject to revision without notice. Please refer to www.csb-battery.com to confirm the latest version.
Seitenansicht 0
1 2

Inhaltsverzeichnis

Seite 1 - UPS123606

Cells Per Unit 6Voltage Per Unit 12Capacity360W @ 5min-rateto Watt(1.60V)/pcs @25°C (77°F)Weight Approx. 1.97 kg(4.34 lbs)Maximum Discharge Current 10

Seite 2 - UPS 123606

Charging ProceduresCharge Voltage(V/Cell)ApplicationTemperature Set Point Allowable RangeMax.Charge CurrentCycle Use25(77 )2.45 2.40~2.50Standby25(77