Cells Per Unit 6
Voltage Per Unit 12
Capacity 40 Ah @ 20hr-rate to 1.75V per cell
Weight Approx. 14.5 kg(32.0 lbs)
Maximum Discharge Current 400A(5sec)
Internal Resistance Approx. 7 mΩ
Operating Temperature Range
Nominal Operating Temperature Range
Float Charging Voltage
Recommended Maximum Charging 12 A
Current Limit
Equalization and Cycle Service 14.4 to 15.0 VDC/unit Average at
Self Discharge
CSB Batteries can be stored for more than 6 months at
25°C (77°F). Please charge batteries before using . For
higher temperatures the time interval will be shorter.
Terminal
L terminal:B2 or Recessed type to accept M6 bolt
Container Material ABS(UL 94-HB) & Flammability resistance of
(UL 94-V0) can be available upon request.
Discharge:
Charge:
Storage:
Constant Current Discharge Characteristics Unit:A (25°C,77°F)
GPL 12400
12V 40Ah
Specification
Powered by
GPL 12400 is a general purpose battery up to 10 years in standby
service or more than 260 cycles at 100% discharge in cycle
service . As with all CSB batteries, all are rechargeable , highly
efficient , leak proof and maintenance free.
13.5 to 13.8 VDC/unit Average at
Width (W)
Dimensions :
Unit: mm (inch)
Overall Height (H) Container height (h) Length (L)
170±2 (6.69±0.08) 168.5±2 (6.63±0.08) 197±2 (7.76±0.08) 165±2 (6.5±0.08)
CSB-manufactured
VRLA batteries are UL-
recognized components
under UL1989.
CSB is also certified by
ISO 9001 and ISO 14001.
(http://www.csb-battery.com)
by TUV CERT according to ISO 9001,ISO 14001.
The system of manufacturer was certified
Constant Power Discharge Characteristics Unit:W (25°C,77°F)
@25°C (77°F)
25°C (77°F)
25°C (77°F)
-15°C~50°C ( 5°F~122°F)
-15°C~40°C ( 5°F~104°F)
-15°C~40°C ( 5°F~104°F)
25°C±3°C (77°F±5°F)
F.V/Time 5MIN 10MIN 15MIN 30MIN 60MIN 90MIN 2HR 3HR 5HR 8HR 10HR 20HR
1.60V
162 103.5 78.2 47.7 28.1 20.4 16.3 11.6 7.36 4.83 3.93 2.03
1.67V
145 96.5 74.5 46.7 27.9 20.3 16.2 11.5 7.34 4.77 3.85 1.94
1.70V
137 92.8 72.4 46.1 27.8 20.2 16.1 11.4 7.32 4.75 3.82 1.91
1.75V
124 87.4 69.5 45.0 27.6 20.1 16.0 11.3 7.29 4.69 3.76 1.84
1.80V
111 81.3 65.9 43.8 27.4 19.9 15.9 11.2 7.25 4.62 3.70 1.77
1.85V
98.1 75.1 62.4 42.5 27.0 19.8 15.8 11.1 7.22 4.56 3.64 1.70
F.V/Time 5MIN 10MIN 15MIN 30MIN 60MIN 90MIN 2HR 3HR 5HR 8HR 10HR 20HR
1.60V
1941 1242 938 572 338 245 195 139 88.4 58.0 47.2 24.4
1.67V
1735 1158 895 558 335 243 194 138 88.1 57.3 46.4 23.3
1.70V
1647 1117 869 552 334 242 193 137 87.9 57.0 46.0 22.9
1.75V
1490 1049 830 539 331 241 192 136 87.5 56.3 45.2 22.1
1.80V
1334 975 791 525 328 239 191 135 87.2 55.6 44.4 21.3
1.85V
1178 902 749 510 324 238 190 134 86.7 54.8 43.7 20.6
RA1403
Ratings presented herein are subject to revision without notice. Please refer to www.csb-battery.com to confirm the latest version.
Drawing of recessed terminal
Seitenansicht 0
1 2

Inhaltsverzeichnis

Seite 1 - GPL 12400

Cells Per Unit 6Voltage Per Unit 12Capacity 40 Ah @ 20hr-rate to 1.75V per cellWeight Approx. 14.5 kg(32.0 lbs)Maximum Discharge Current 400A(5sec)Int

Seite 2 - GPL12400

C h a r g e V o l t a g e ( V / C e l l ) A p p l i c a t i o n T e m p e r a t u r e S e t P o i n t A l l o w a b l e R a n g e M a x . C h a r g

Kommentare zu diesen Handbüchern