Csb-battery GPL1272 Bedienungsanleitung

Stöbern Sie online oder laden Sie Bedienungsanleitung nach Stromversorger Csb-battery GPL1272 herunter. CSB Battery GPL1272 User Manual Benutzerhandbuch

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 2
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 0
Cells Per Unit 6
Voltage Per Unit 12
Capacity 7.2Ah @ 20hr-rate to 1.75V per cell
Weight Approx. 2.6 kg(5.73 lbs)
Maximum Discharge Current 100A/130A(5sec)
Internal Resistance Approx. 21 mΩ
Operating Temperature Range
Nominal Operating Temperature Range
Float Charging Voltage
Recommended Maximum Charging 2.16A
Current Limit
Equalization and Cycle Service 14.4 to 15.0 VDC/unit Average at
Self Discharge
CSB Batteries can be stored for more than 6 months at
25°C (77°F). Please charge batteries before using . For
higher temperatures the time interval will be shorter.
Terminal F1/F2-Faston Tab187/250
Container Material ABS(UL 94-HB) & Flammability resistance of
(UL 94-V0) can be available upon request.
Discharge:
Charge:
Storage:
Constant Power Discharge Characteristics Unit:W (25°C,77°F)
Constant Current Discharge Characteristics Unit:A (25°,77°F)
GPL 1272
12V 7.2Ah
Specification
Powered by
GPL 1272 is a general purpose battery up to 8 years in standby
service or more than 260 cycles at 100% discharge in cycle
service . As with all CSB batteries, all are rechargeable , highly
efficient , leak proof and maintenance free.
13.5 to 13.8 VDC/unit Average at
Dimensions :
Unit: mm (inch)
CSB-manufactured
VRLA batteries are UL-
recognized components
under UL1989.
CSB is also certified by
ISO 9001 and ISO 14001.
F.V/Time 5MIN 10MIN 15MIN 30MIN 60MIN 90MIN 2HR 3HR 5HR 8HR 10HR 20HR
1.60V
24.1 19.2 15.6 9.05 4.87 3.43 2.67 1.93 1.29 0.90 0.73 0.37
1.67V
23.1 18.3 14.9 8.80 4.72 3.33 2.60 1.89 1.28 0.88 0.72 0.36
1.70V
22.6 17.8 14.5 8.68 4.65 3.28 2.56 1.87 1.27 0.87 0.72 0.36
1.75V
21.8 17.0 13.9 8.45 4.52 3.20 2.50 1.82 1.23 0.86 0.70 0.36
1.80V
20.8 16.2 13.2 8.19 4.39 3.13 2.46 1.77 1.20 0.84 0.69 0.35
1.85V
19.6 15.3 12.5 7.87 4.27 3.04 2.39 1.74 1.16 0.82 0.67 0.34
F.V/Time 5MIN 10MIN 15MIN 30MIN 60MIN 90MIN 2HR 3HR 5HR 8HR 10HR 20HR
1.60V
258 210 173 103 54.0 38.1 29.8 22.0 15.3 10.5 8.78 4.46
1.67V
251 202 166 101 53.3 37.4 29.1 21.8 15.0 10.4 8.64 4.40
1.70V
247 199 162 99.3 52.9 37.1 28.8 21.6 14.9 10.2 8.57 4.36
1.75V
240 192 156 97.4 52.3 36.5 28.2 21.2 14.5 10.1 8.45 4.28
1.80V
231 185 151 95.0 51.5 35.8 27.7 20.8 14.1 10.0 8.29 4.20
1.85V
222 177 146 92.2 50.6 35.2 27.2 20.4 13.8 9.72 8.14 4.12
@25°C (77°F)
25°C (77°F)
25°C (77°F)
-15°C~50°C ( 5°F~122°F)
-15°C~40°C ( 5°F~104°F)
-15°C~40°C ( 5°F~104°F)
25°C±3°C ( 77°F±5°F)
RA1312
Ratings presented herein are subject to revision without notice. Please refer to www.csb-battery.com to confirm the latest version.
Width (W)Overall Height (H) Container height (h) Length (L)
98.6±1.5 (3.88±0.06) 94.3±1 (3.71±0.04) 151±2 (5.94±0.08) 64.8±1 (2.55±0.04)
(http://www.csb-battery.com)
by TUV CERT according to ISO 9001,ISO 14001.
The system of manufacturer was certified
Seitenansicht 0
1 2

Inhaltsverzeichnis

Seite 1 - GPL 1272

Cells Per Unit 6Voltage Per Unit 12Capacity 7.2Ah @ 20hr-rate to 1.75V per cellWeight Approx. 2.6 kg(5.73 lbs)Maximum Discharge Current 100A/130A(5sec

Seite 2 - 12V 7.2Ah

Charge Voltage(V/Cell) Application Temperature Set Point Allowable Range Max.Charge Current Cycle Use 25(77 ) 2.45 2.40~2.50 Standby 25(77 ) 2.275

Kommentare zu diesen Handbüchern

Keine Kommentare